Digital communicator JA-65X 4/7 MFM53102
The Surgard protocol has 4/2 structure plus one more digit
which is generated automatically (see 4.3)
If the control panel is split and only one section is armed,
then a partial arming report code is sent. If all sections are
armed, a complete arming report code is sent. If the
system was completely armed and only one section is
disarmed, the disarming report code will be sent and then
it will be followed by the partial arming report code.
The pulse formats are not capable to report zero and
numbers above 15. For this reason events in zone 16 or in
a subsystem are reported to the Monitoring Station as
events in zone 10. This means that from the point of view
of the monitoring station zone 10 also covers zone 16 and
the subsystem if used. This problem does not exist in the
CID protocol.
If the system is arming while there is a bypass, partial
arming will be reported to the CMS (also stored to the
internal memory)
Factory setting: 00 for all events
4.2 Account ID code setting
sequence: 02
This sequence is used for the alarm system identification by a
Monitoring Station. The sequence structure: 02 x x x x
where:
xxxx – account ID code ( x are numbers from 0 to 9 or
hexadecimals).
When using only three-digit codes (formats 3/1 and 3/2) enter
a zero in the first position. The communicator will then ignore it
(example - 0123)
Note: Changing of the account code erases the internal
communicator’s memory of non reported events and sends a
„Reset“ reporting code (051) to the Monitoring Station. If pulse
formats are used, zero is transmitted as A
h
Factory setting: 0000
4.3 Protocol and Format setting
sequence: 03
This sequence is used to select the communication protocol
and format. Its structure is as follows: 03 x y
where:
x - protocol (0 – 9, see table bellow)
y - format (0 - 3 see table on right)
Notes:
Some Monitoring Station receivers do not support all formats.
Logic of the format marking - 4/2 means that an account code has
4 digits and an event report code has 2 digits.
Changing of a format erases the internal communicator’s memory
of non reported events and sends a “Reset“ reporting code (051)
to the Monitoring Station.
Factory setting: 90 (Contact ID)
4.4 Re-dialing pause setting
sequence: 04
If a dialer is triggered it attempts to make a connection
(alternating between the primary and the backup telephone
number). If it is not possible to make a connection after 8
attempts, a pause is initiated. After this pause the dialer will
attempt again. If any event triggers the communicator during the
pause, the pause ends immediately. The pause length can be set
in the following way:
0 4 x
where:
x – time multiplied by 10 minutes (from 1 to 9, example 3 =
30 minutes)
Factory setting: 1 = 10 min.
4.5 CMS phone number entering
sequence: 06
Central monitoring station modem phone numbers can be
stored by entering the following sequence: 0 6 x x .... x F y
where:
xx...x = Central Monitoring Station phone number (up to
16 digits)
y = 1 for primary phone number memory
2 for back up phone number memory
Pause (3 sec.) can be inserted into the telephone number by
entering F0. It is also possible to insert the * tone by F7 or the
# tone by F8 if requested for DTMF dialing.
Example: number 02 123456 as main Monitoring Station
number is entered with 06 02 F0 123456 F1.
Phone number erasing: 0 6 F 0 F y
where:
y = 1 to erase the primary telephone number
2 to erase the back up telephone number
Protocols
x Name
Hand-
shake
Data Kiss off Speed
format
0
Ademco Slow
(Silent Knight)
1400Hz 1900Hz 1400Hz 10bps
Next
table
1
Ademco Fast 1400Hz 1900Hz 1400Hz 14bps
Next
table
2
Telemax 2100Hz 1650Hz 2100Hz 10bps
Next
table
3
Franklin 2300Hz 1800Hz 2300Hz 20bps
Next
table
4
Radionics 2300 2300Hz 1800Hz 2300Hz 40bps
Next
table
5
Radionics 1400 1400Hz 1900Hz 1400Hz 40bps
Next
table
6
DTMF 2300 2300Hz DTMF 2300Hz DTMF
Next
table
7
Surgard* 2300Hz DTMF 2300Hz DTMF
4/3
8
Ademco express* Dual tone DTMF 1400Hz DTMF
4ID/2
9
Contact ID* Dual tone DTMF 1400Hz DTMF
CID
* fixed format, “y” is arbitrary (0 is recommended)
Formats
y
format reports structure
0
3/1
Major events only
xxx R
1
3/2
All events
xxx rc
2
4/1/1
Major events with autom. source
identification
xxxx Rn
3
4/2
All events
xxxx rc
xxxx = account number
R = major event code (only first digit counts)
rc = detailed event code (two digits)
n = source identification (generated automatically)
Surgard protocol has structure: xxxx E rc, where E is a group
identifier (generated automatically)
E Event Note
1 Fire
2 Panic
3 Alarm General
4 Arming Incl. Partial
5 Disarming
6 Failure Power failure, RF jamming …
8 Report Enter/Exit service mode …
9 Restore End of alarm, panic …
A Test 24 hour test
4

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Jablotron JA-65X bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Jablotron JA-65X in de taal/talen: Engels als bijlage per email.

De handleiding is 0,17 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info