Digital communicator JA-65X 3/7 MFM53102
Notes: Remote access connection can also be enabled by the
alarm system user (regardless of the above setting) by entering
89 while in the user mode, when the phone rings. If you use
another telephone set on the same telephone line, it should be
switched to the tone dial mode.
Factory setting: 0 = never answer
3.2 Remote access code setting
sequence: 07
In order to access the panel remotely, it is necessary to
authorize the access with an 8-digit access code. This code is
compared with the one programmed in the control panel. If the
caller tries to access the panel with another code, the
connection will be terminated immediately. A wrong code alarm
will be triggered on the control panel after the 5
th
unsuccessful
attempt to dial in. Store your access code to the control panel by
entering: 0 7 xxxxxxxx
where:
x x . . . . . x - any 8 digits access code
Factory setting: 00000000
4 Central monitoring station
communication setting
This part of the manual is intended only for specialists involved
in monitoring. We recommend to use a computer equipped with
Comlink program for complete setting of the monitoring station
communication.
Changes of the setting can also be performed manually using
the keypad:
Enter programming mode when disarmed (F 0 Service
Code, factory default 6060), indicated by a “P“.
To exit programming press the N key (“P“ will turn off).
Central monitoring station communication parameters
Sequence Description Factory default setting
0 001 xx
to
0 198 xx
Reporting codes table (see part 5)
where: x= 0 9, F0 = A
h
, F1 = B
h
, F2 = C
h
, F3 = D
h
, F4 = E
h
, F5 = F
h
if 00 is set, the event is not reported
00
For all events
0 2 xxxx
Account ID code (4 digits, for 3/1 and 3/2 formats the structure is 0xxx)
x = 0 9 (hexadecimal codes can be used too - see above)
0000
0 3 xy Protocol x:
0 = Ademco Slow
1 = Ademco Fast
2 = Telemax
3 = Franklin
4 = Radionics
2300
5 = Radionics 1400
6 = DTMF 2300
7 = Surgard
8 = Ademco
Express
9 = Contact ID
Format y:
0 = 3/1 (xxx R)
1 = 3/2 (xxx rc)
2 = 4/1/1 (xxxx Rn)
3 = 4/2 (xxxx rc)
90
Contact ID
0 4 x Re-dialing pause, x= 1 – 9 (x 10 min.)
1 10 minutes
0 6 xx..xFy CMS phone numbers xx...x to memory y (1 and 2), pause = F0
erased
0 9 6060
Communicator reset to factory default settings
Notes:
Some of the protocols are not standardized and some
manufacturers of Monitoring Station receivers use different
parameters in some of their protocols. Therefore Jablotron
cannot guarantee full compatibility with all Central Monitoring
Station receivers.
If the connection with the Monitoring Station is not available,
the events are queued in the communicator’s memory and are
transmitted in one burst as soon as the connection is
established. All events are reported to the Monitoring Station in
the same order as they happened.
Once communication has started, it can not be interrupted
unless the control panel is switched to the programming or to
the user mode. For example, if the user causes a false alarm
and then cancels it, both events are sent to Monitoring Station.
Events occurring while the control panel is in the
programming or user mode are reported to the Monitoring
Station after the closing of these modes. (They are stored in
the memory and reported together with reporting codes
describing the change of operation modes.)
When the dialer is activated, the communication to the
monitoring station has the highest priority (voice and SMS
messages are sent later with lower priority). A User or Installer
can interrupt the digital dialer communication by entering the
User mode or Programming mode. Reset of the control panel
has no influence to the digital communicator’s settings (it is
reported to the Monitoring station as an event).
The RESET of the digital communicator itself (sequence 0
9 6060), the change of the Monitoring Station’s telephone
numbers, the change of an account number code or the
change of a format setting will erase all the reporting codes
queued in the communicator’s memory. However the events
remain stored in the control panel’s internal memory.
Jablotron recommends use of the MS-350 monitoring
station with ComGuard SW.
4.1 Reporting codes setting
sequences: 00 and 01
These sequences can be used to program the report codes for
all possible events. Depending on the used protocol and
format, different amounts of data should be entered. The
complete report code programming table is shown in section 5.
The setting sequence structure is as follows: 0 x x x r c
where:
xxx = event number (from 001 to 198)
rc = report code (two digits). For 3/1 and 4/1/1 formats
only the first digit of the report code is used (R).
Codes should be entered in a hexadecimal
format, with numbers higher than 9 beginning
with the F key: A
h
= F0 B
h
= F1 C
h
= F2 D
h
=
F3 E
h
= F4 F
h
= F5
If the reporting code 00 is programmed, the event will not be
reported to the Monitoring Station.
Notes:
Abbreviation "Rc" is used in the report code programming
table for the major events group. Only the first digit of this
group of codes is transmitted when formats 3/1 or
4/1/1are used. Other formats use both digits of the "Rc"
and "rc" report codes.
The Contact ID (CID) is an automatic protocol. If you enter
any report code other than zero for a major event (Rc), all
events of this type will be transmitted automatically
including all details regarding the event source. Internal
structure of the CID protocol is shown in part 1.1. This
protocol provides the most in-depth data for the monitoring
station and its use is recommended by Jablotron.
3

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Jablotron JA-65X bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Jablotron JA-65X in de taal/talen: Engels als bijlage per email.

De handleiding is 0,17 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info