41497
5
Verklein
Vergroot
Pagina terug
1/24
Pagina verder
CE1G2267xx 28.08.2002 5/24
On the heating engineer level, change from the flashing
CAL symbol to the volume adaption symbols by rolling
several times toward the display.
Press to accept.
(factory setting) will flash. Press
to accept or continue rolling until you reach
or .
Press to accept (also refer to Fig.
).
Normally sized controlled system
(factory setting):
Normal rooms, normal (steel pipe) radiators and
buildings with average insulation.
Fast controlled systems:
For small rooms, light (plate) radiators, well
insulated builgings or fan coil units.
Slow controlled systems:
For large rooms, heavy (cast iron) radiators,
poorly insulated buildings and large masses.
Control gain (adaption of heat output)
On the heating engineer level, change from the flashing
CAL symbol to the heat output adaption symbols by rolling
away from the display.
Press to accept. Symbol
(factory setting) will
flash. Press to accept or continue rolling toward the display
until you reach
or . Preess to accept (also
refer to Fig.
).
Normally sized heat output (standard)
Oversized heat output:
For high boiler / flow temperatures, oversized
heating surfaces or oversized volumetric flow
(nominal valve size).
Undersized heat output:
For low boiler / flow temperatures, too small
heating surfaces or too small volumetric flow
(nominal valve size).
4.2.2 Frost protection mode
Use operating mode selector to select symbol
(also refer to Fig ).
If the standard value of 5 °C need to be changed, the frost
protection setpoint
must be changed via temperature
menu T (refer to the Operating Instructions).
5. Replacing the controller
Proceed according to Fig. G.
6. Functional check
a) Check the display. If there is no display, check the
correct fitting and function of the batteries.
b) Comfort mode
c) Select temperature menu T and adjust the temperature
setpoint
to 29 °C (refer to the Operating
Instructions)
d) The controller must deliver an OPEN signal
for
about 150 seconds, and the regulating unit must run to
its limit position. If this is not the case:
Check regulating unit and wiring
Room temperature may be higher than 29 °C
e) Select temperature menu T and adjust the temperature
setpoint
to 5 °C (16 °C in case of set value
limitation)
f) The controller must deliver a CLOSE signal
for
about 150 seconds, and the regulating unit must run to
its limit position. If this is not the case:
Check regulating unit and wiring
Room temperature may be lower than 5 °C
(16 °C in the case of set value limitation)
g) Reset the setpoint temperature
to the initial value
(standard value 19 °C or individual setting)
h) Select the required operating mode
7. Reset
User-defined data:
Press the button behind the pin opening for at least one
second: this resets the user-specific settings to their
default values (the heating engineer settings will not
changed). The clock starts at 12:00. During the reset time,
all sections of the display light up, enabling them to be
checked.
All user-defined data plus the heating engineer
settings:
Press the button behind the pin opening together with the
warmer and colder buttons for at least one second.
After this reset, the factory settings will be reloaded (also
refer to section “Factory settings“).
After every reset the controller starts to an initialization
phase of 180 seconds. During this phase, the actuator is
driven to its fully closed position.
Important: The actuator reaches the fully closed position
within a maximum of 150 seconds.
After every reset the controller must be slid
back onto its base within 30 seconds.
8. Notes
REV33 is an electric weekly programmable room
temperature controller.
The controler conforms to “Software Class A” and is for
use in “normal” pollution situation.
If the reference room is equipped with thermostatic
radiator valves, they must be set to their fully open
position
The remote operation contact T1 / T2 must be wired
separately using a separate screened cable
Ensure that the local regulations for electrical
installations are complied with
Mise en service
1. Montage
Retirer l'appareil de son socle, procédez comme indiqué
figure A.
Pour le montage, référez-vous aux figures B et C.
(voir également instructions de montage)
2. Vérifier le câblage
Les schémas de raccordement figurent au chapitre
"Schéma de raccordement". Voir aussi figures D et E.
5

Hulp nodig? Stel uw vraag in het forum

Spelregels
1

Forum

Siemens-REV33

Zoeken resetten

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens REV33 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens REV33 in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Spaans, Pools, Deens als bijlage per email.

De handleiding is 0,79 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van Siemens REV33

Siemens REV33 Gebruiksaanwijzing - Nederlands - 2 pagina's

Siemens REV33 Gebruiksaanwijzing - Français - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info