485934
2
Verklein
Vergroot
Pagina terug
1/2
Pagina verder
Do you want to view the programmable timer settings?
CE1B3058en / 17.11.2005 Subject to alteration Building Technologies / HVAC Products
Do you want to reload the default timer settings?
+
1.
Set the controller to standby .
2. Press and simultaneously for 3 seconds. Release them and, within 2
seconds, press 2 times
.
Day/s
Time when controller is in normal operation
Mo (1) – Fr (5) 06:30 – 08:30 (A1) 17:30 – 22:30 (A2)
Sa (6) 08:00 – 23:00 (A3)
Su (7) 08:00 – 22:30 (A4)
Default
settings
- in the remaining time controller is in energy saving
- timer A5…A8 are free, no default setting
Changing the control parameters
To optimize the control performance, a number of control parameters can be adjusted. This can
also be made during operation without opening the controller.
If you want to change the control parameters, proceed as follows:
(For factory settings, see table on the right-hand side)
+
/
+
+
1. Set the controller to standby
2. Press
and simultaneously for a minimum of 3 and a
maximum of 5 seconds. Release them and, within 2 seconds, press
the
again for 3 seconds. The display will show “P01”.
3. Select the required parameter by repeatedly pressing the
or button:
P01 P02 P22 P98
+-+
--
+
3057z03
P99
-
+
-
P25
+-
4. Press
and simultaneously. The current value of the selected
parameter will appear, which can be changed by repeatedly pressing
or .
5. By pressing
and simultaneously again or 5 seconds.
after the last press of a button, the last parameter will be displayed
again.
6. If you wish to display and change additional parameters,
repeat steps 3 through 5.
7. 10 seconds after the last display or setting, all changes are
stored and the controller will return to standby.
8. Switch to normal operation with the button.
Recalibrating the sensor
If the room temperature displayed by the controller does not agree with the temperature effectively
measured, the temperature sensor can be recalibrated. For that purpose parameter P07 must be
changed.
Proceed as described under “Changing the control parameters” and follow steps
1 through 3 to select parameter P07.
With step 4, the room temperature displayed can now be matched to the
temperature effectively measured. Each push of the
or button changes
the temperature by + or – 0.5 °C up to a maximum of + / - 3 °C.
With step 7, the recalibration is automatically stored 10 seconds after the last
readjustment.
Commissioning (by qualified HVAC staff) (all temperature settings can be made in increments of 0.5 K)
Para-
meter
Controller’s parameter factory settings: Setting range RDF210 RDF210.2
P01 Setpoint of heating in energy saving mode (Wheat
Eco
) 16 OFF, 5 °C…Wcool
Eco
P02 Setpoint of cooling in energy saving mode (Wcool
Eco
) 28 OFF, Wheat
Eco
…40 °C
P03
Setpoint of heating in standby
(Wheat
Stb
)
OFF OFF, 5 °C…Wcool
Stb
P04
Setpoint of cooling in standby
(Wcool
Stb
)
OFF OFF, Wheat
Stb
…40 °C
P05 Minimum setpoint limitation in normal operation (Wmin
Norm
) 5 °C 5 °C…Wmax
Norm
P06 Maximum setpoint limitation in normal operation (Wmax
Norm
) 35 °C
Wmin
Norm
…40 °C
P07 Sensor calibration 0 K
-3…+3 K
P08 Switching differential heating SDH 2 K
0.5…+4K
P09 Switching differential cooling SDC 1 K
0.5…+4K
P10 Switching differential fan speed 2 in heating operation mode SDH2 1 K
0.5…+4K
P11 Switching differential fan speed 2 in cooling operation mode SDC2 1 K
0.5…+4K
P12 Switching differential fan speed 3 in heating operation mode SDH3 1 K
0.5…+4K
P13 Switching differential fan speed 3 in cooling operation mode SDC3 1 K
0.5…+4K
P14 Dwelling time of auto fan speeds 2 min.
1…5 minutes
P15 Minimum output on-time (Y11) 1 min.
1…10 minutes
P16 Minimum output off-time (Y11) 1 min.
1…10 minutes
P17 Selection of °C or °F °C °C or °F
P18 Display of temperature or setpoint ON
OFF: Setpoint
ON: Room (or return air)
temperature
P20 Fan control in energy saving mode OFF
OFF in dead zone
ON in dead zone
P21 Fan control in normal operation OFF
OFF in dead zone
ON in dead zone
P22 Heating / cooling mode
1:
Cooling
only
0: Heating only
1: Cooling only
2: Automatic c/h changeover
X
P23 Heating / cooling changeover switching point cooling 16°C 10…25 °C
X
P24 Heating / cooling changeover switching point heating 28°C 27…40 °C
X
P25 Infrared receiver (only with RDF.../IR) 1
0: Disabled
1: Enabled
P98 Active temperature sensor
Diagnostic
value
0: Internal sensor
1: External sensor
P99
Value of current heating / cooling changeover temperature
reading or indication of current mode
Diagnostic
value
100 = input open Æ mode
0…49 °C = cur. temp. value
00 = input bridged Æ
mode
OFF= not commissioned as
automatic c/h changeover
X
Press the button to sequentially review the 8 auto timers.
Legend to table
Adjustable: Please record all changes you make
Not adjustable / display only
X
Not adjustable / no display
2

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Siemens RDF 210 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Siemens RDF 210 in de taal/talen: Engels als bijlage per email.

De handleiding is 0,51 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van Siemens RDF 210

Siemens RDF 210 Gebruiksaanwijzing - Deutsch - 2 pagina's

Siemens RDF 210 Gebruiksaanwijzing - Français - 2 pagina's

Siemens RDF 210 Installatiehandleiding - Alle talen - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info