INSTALLER’S SETTING OPTIONS
209
ENGLISH
208
INSTALLER’S SETTING OPTIONS
Fan operation in the cooling mode and thermal off conditions
(air conditioner)
It is a function that sets the indoor unit fan movement, in cooling mode, when thermal is off.
● Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for
3seconds or longer to enter the installer function.
● Select remote controller code value ‘35’.
- You can press ‘▲’, ‘▼’ button to change the code value.
● In value1, use ‘▲’, ‘▼’ button to select setting value, and press ‘Done’ button to complete set-
ting.
- If you do not press ‘Done’ button, the setting value will not be applied.
Value
Fan operation in the cooling mode
and thermal off conditions
0 Fan speed Low
1 Fan off
2 Fan speed Setting value
Primary Heater control setting(air conditioner)
It is a function that sets the outdoor unit to operate with auxiliary heat source and the heater to
run with main heat source in heating mode.
● Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for
3seconds or longer to enter the installer function.
● Select remote controller code value ‘36’.
- You can press ‘▲’, ‘▼’ button to change the code value.
● In value1, use ‘▲’, ‘▼’ button to select setting value, and press ‘Done’ button to complete set-
ting.
- If you do not press ‘Done’ button, the setting value will not be applied.
Value Primary Heater control setting
000 Cancel primary heater control
001 Use primary heater control