JA-83K control panel installation manual - 7 - MKG51101
The control panel must have its antenna connected and it must be in
Service mode (If this is not the case, enter *0 service code (factory
default: 8080). The control panel must be disarmed).
Enter the appropriate programming sequences – see the following
description (an unfinished sequence can be escaped from by pressing
the # key).
To exit Service Mode press the # key.
6.1 Exit delay time
An exit delay time occurs while setting (arming) the system. During this
time period delayed or next-delayed detectors can be triggered without an
alarm occurring. To program the delay time, enter:
2 0 x
where x is a number from 1 to 9 determining the duration in steps
of tens of seconds (1=10 s, 2=20 s,....)
If there is a final-door detector in the system then the exit delay is
multiplied by 30 s instead (1=30 s, 2=60 s,...).
Example: To program a 20 seconds exit delay, use the sequence 202 (if
there is a final-door detector, a 60 seconds delay will result).
Factory default setting: x = 3
6.2 Entrance delay time
The entrance delay time is provided to unset (disarm) the system after a
first delayed detector has been triggered. To program this time, enter:
2 1 x
where x is a number from 1 to 9 determining the delay in multiples
of 5 seconds (1=5 s, 2=10 s,....)
If the entrance delay is triggered by a final-door detector, then parameter
x is multiplied by 30 s instead. (1=30 s, 2=60 s,...) – in this case it means that
the entrance delay would be six times longer than if it had been triggered by
an ordinary detector.
Example: To program a 20 seconds entrance delay, enter the sequence 214
(if the delay has been activated by a final-door detector, a 120 seconds delay
will result instead).
Factory default setting: x = 4
6.3 Alarm duration time
This parameter limits the duration of a triggered alarm. After the alarm
state expires, the control panel will return to its previous state, i.e. as before
the alarm occurred. The alarm state can also be terminated by an authorised
user. To program the alarm duration enter:
2 2 x
where x is a number from 0 to 9 determining the alarm duration:
0 = 10 s, 1 = 1 min., 2 = 2 min. up to 8 = 8 min., 9 = 15
min.
Note: There can be up to 5 different alarms in the system: intruder, tamper,
fire, panic, and technical alarm.
Example: Alarm duration of 5 min. = sequence 225
Factory default setting: 4 minutes
6.4 PGX and PGY functions
The functions of PGX and PGY can be programmed by entering
sequences:
2 3 x for PGX
2 4 x for PGY
where x determines the PG function or the event which triggers a
change of PG state:
x Unsplit system Split system
0
Completely (ABC) set = PG on Alarm A = PG on
1
Anything set = PG on Alarm B = PG on
2
AB set (not ABC) = PG on Entrance delay A = PG on
3
Fire alarm = PG on Entrance delay B = PG on
4
Panic = PG on A set = PGX on, B set = PGY on
5
Any alarm = PG on
(excluding Panic)
Panic A = PGX on
Panic B = PGY on
6
AC dropout = PG on Fire = PGX on, dropout = PGY on
7*
ON/OFF
8*
2 seconds pulse
fig. 9 PG outputs settings
* The ON / OFF and 2 second pulse functions can be controlled from
the keypad by keying in * 8, *9 or using the ON and #OFF keys (see 6.26)
or th
ey can be operated by a code or card. These PG output functions can
also be controlled by signals from keyfobs or detectors (see6.40).
Notes:
The PGX and PGY outputs are not only provided as control panel
terminals, but the signals are also wirelessly transmitted for UC and AC
modules.
The status of PGX and PGY outputs can be displayed by pressing the
“?” key. The names of the outputs can be edited – see 6.47.
Ex
ample (for unsplit systems): Assigning an ON/OFF function to the PGX
output = sequence 237. Assigning a panic function to the PGY output =
sequence 244.
Factory default setting: PgX= ON/OFF, PgY= anything set
6.5 Changing telephone numbers in maintenance
mode
If the control panel is equipped with a JA-8xY, JA-80V or JA-80X
communicator, then this sequence enables the holder of the master code
(system administrator) to program telephone numbers for alarm reporting in
maintenance mode. Programming telephone numbers is the same as in
Service mode (see communicator manual):
2 5 1 programming enabled
2 5 0 programming disabled
Factory default setting: programming disabled.
6.6 Radio interference indication
The control panel is capable of detecting and indicating radio
communication jamming. If this function is enabled, any radio jamming longer
than 30 s will trigger fault indication and if armed the alarm is triggered.
2 6 1 enabled
2 6 0 disabled
Factory default setting: disabled.
Note: In some places the system can be permanently or occasionally
affected by radio interference, e.g. by nearby radar stations, TV transmitters
etc. In most cases the system can tolerate such effects, but with this anti-
jamming function disabled.
6.7 Radio communications supervision
If enabled, the control panel can routinely check wireless connections to
its devices. If communication with a particular device is lost, the control panel
can communicate a fault indication to the user:
2 7 1 indication enabled
2 7 0 indication disabled
Notes:
In the OASiS system, communication is checked every 9 mins.
In detectors used for car protection, (JA-85P, JA-85B) it is possible to
disable radio communication supervision. It allows car detectors to be
excluded from supervision to avoid alarm triggering when driving the
car away from the system.
Random dropouts in communication can occur in some installations
near e.g. airports or TV towers. The system is still reliable in such
situations as high-priority transmissions are repeated often. We
recommend disabling communications supervision in cases like this.
Factory default setting: supervision disabled.
6.8 RESET enabled
If resetting is enabled, it is possible to return the control panel to its
original factory-default settings via the reset link on the main board. (see
section 3.8).
2 8 1 RESET enabled
2 8 0 RESET disabled
Warning: If resetting is disabled and the service code has been forgotten, it
would no longer be possible to enter Service mode. If this happens, send the
control panel back to the manufacturer.
Factory default setting: RESET enabled.
6.9 Enrollment to a sub control panel for setting
control
If the control panel has another OASiS control panel enrolled as a sub-
system, then the sub-system reports all alarms, tampering and faults to the
master control panel. The master control panel reacts to particular signals
accordingly, and displays the sub control panel’s address as the source.
After sub control panel enrollment to the master control panel, these two
panels are independent concerning setting control. Each panel can be
operated by its own keypads or key fobs. If there is an alarm or fault in the
sub control panel, it is also indicated on the master control panel. In this
configuration it is impossible to control the sub control panel from the master
control panel.
7

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Jablotron JA-83K bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Jablotron JA-83K in de taal/talen: Engels als bijlage per email.

De handleiding is 1,55 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info