Heatronic 4000 7738003455 (2014/04)4 of 60
Modulation Delay
---------------------------------
The MOD DELAY is the time that the boiler burner must hold
the modulation of the boiler at a minimum before allowing it to
modulate any further.
Boiler Mass
--------------------------------------
The Boil MASS setting selects the thermal mass characteristics
of each boiler. Operation of the boiler can become unstable if the
incorrect Boiler Mass setting is chosen. A key sign of unstable
boiler operation is that the flame will continue to increase & then
decrease in short periods of time. By choosing a lower boiler
mass setting, the boiler response will become more stable.
LOW (GB Series)
The LO setting is selected if the boiler that is used has a low
thermal mass. This means that the boiler has very small water
content & has very little metal in the heat exchanger. A boiler that
has a low thermal mass comes up to temperature quite rapidly
when fired. This is typical of many copper fin-tube boilers.
The Low mass setting (LO) provides a fast response to the
heating system.
MED
The MED setting is selected if the boiler that is used has a
medium thermal mass. This means that the boiler either has
a large water content & a low metal content or a low water
content & a high metal content. This is typical of many modern
residential cast iron boilers or steel tube boilers.
The Med mass setting provides a moderate response to the
heating system.
HI (SB and G Series)
The HI setting is selected if the boiler that is used has a high
thermal mass. This means that the boiler has both large water
content & a large metal content. A boiler that has a high thermal
mass is relatively slow in coming up to temperature. This is
typical of many commercial cast iron & steel tube boilers.
The Hi mass setting provides a slow response to the heating
system.
Low Fire & High Fire Boiler Output
---------------
In order to accommodate different boiler capacities in the
same system, a low fire & high fire boiler output for each boiler
can be set. This allows the control to properly operate the
boilers using either sequential or parallel modulation. Each
boiler typically has a rating plate that specifies the minimum
& maximum output. This information is also available in the
boiler manual.
The minimum & maximum boiler output is expressed in MBtu/h.
1 MBtu/h = 1,000 Btu / hour. The range is from 10 MBtu/h to
9,990 MBtu/h.
For example, if a boiler has a maximum output of 100,000
Btu / hr & a minimum output of 20,000 Btu / hr (turn down
ratio of 5):
Maximum Boiler Output = 100,000 = 100 MBtu/h
1,000
Minimum Boiler Output = 20,000 = 20 MBtu/h
1,000
Motor Speed
-------------------------------------
The MOTOR SPD is the amount of time the boiler requires to
go from 0% modulation to 100% modulation.
Gas valve actuating motors have a design time from fully
closed to fully opened which can be found in the manufacturer’s
manual. The Motor Speed should be set to this time.
The Motor Speed setting for a Variable Frequency Drive (VFD)
is the amount of time required to go from a stopped position
to 100% fan speed. Since a VFD has a very quick response
rate, it may be necessary to increase the Motor Speed setting
in order to increase the stability of the boiler modulation.
OR
Start Modulation
-- - -- - -- - - - - - - -------------------
The START MOD setting is the lowest modulation output required
to obtain proper ignition. Whenever boiler operation is required,
the control outputs an analog signal corresponding to the Start
Modulation setting & closes the boiler contact to turn on the
burner. After the Fire Delay has elapsed & the burner is ignited,
the control modulates the firing rate between the Minimum
Modulation setting & the Maximum Modulation setting.
Minimum Modulation
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
The MIN MOD is the lowest signal the control can send to
modulate the boiler. This operates the boiler at low fire. Use the
MIN MOD setting in the Adjust Menu to select an appropriate
boiler minimum modulation.
Refer to the boiler manufacturer’s literature to determine
the minimum output voltage V (dc) or current (mA) that the
boiler will successfully operate at.
For 0 to 10 V (dc):
Minimum Modulation =
Boiler’s Minimum Input Signal
x 100%
10 V (dc)
For 4 to 20 mA:
Minimum Modulation =
Boiler’s Minimum Input Signal - 4mA
x 100%
16 mA
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire.
The boiler can be modulated to 10 V (dc) where it reaches
high fire.
Minimum Modulation = 1.8 V x 100% = 18%
10 V
Control’s
Output
Signal
Range
Boiler’s
Input
Signal
Range
100%
10 V (dc)
10 V (dc)
0 V (dc)
88%
Boiler’s
Minimum
Input
Signal
Minimum
Modulation
0%
1.8 V (dc)
18%
4

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Bosch Heatronic 4000 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Bosch Heatronic 4000 in de taal/talen: Engels als bijlage per email.

De handleiding is 7,85 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van Bosch Heatronic 4000

Bosch Heatronic 4000 Gebruiksaanwijzing - Français - 60 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info