Dial Thermostat
Model: HTR230
INSTALLER MANUAL
SALUS Controls plc
SALUS House
Dodworth Business Park South,
Whinby Road,
Dodworth, Barnsley S75 3SP, UK.
Sales: T: +44 (0) 1226 323961
E: sales@salus-tech.com
Technical: T: +44 (0) 1226 323961
E: tech@salus-tech.com
www.salus-controls.com
SALUS Controls is a member of the Computime Group
Maintaining a policy of continuous product development SALUS Controls plc reserve the right to
change specification, design and materials of products listed in this brochure without prior notice.
Issue Date: Dec 2015
00190
For PDF Installation guide please
go to www.salus-manuals.com
8. Technical Specification
Model: HTR230
Voltage:
230 V AC, +-10%, 50/60 Hz
Operating Performance:
230 V: 1,8 W
Temperature setback:
Temperature range:
2°C-4°C
5°C- 30°C
Span:
+/- 0,5°C
Calibration:
Yes, with jumper
Storage temperature:
-20°C to +60°C
Ambient temperature:
0 °C up to 45 °C
Degree of protection:
IP 30
CE conformity according to:
Class II ( EN60730 )
Housing material:
PC, V2
Color:
RAL 9010 pure white
Connection:
Screw terminal
Weight
90g net / 135g gross
Puls-wide-modulation:
(PWM)
Yes
Valve protection:
Heating and Cooling:
Cooling blocked:
Dimensions:
Yes
Yes, automatically Change Over on the CO terminal
Yes, with jumper
85mm*85mm*25mm
Warranty
SALUS Controls warrants that this product (HTR230) will be free from any
defect in materials or workmanship, and shall perform in accordance with
its specification, for a period of five years from the date of installation.
SALUS Controls sole liability for breach of this warranty will be (at its option) to repair
or replace the defective product.
Customer Name: ......................................................................................................................................................
Customer Address: .................................................................................................................................................
............................................................................................................................................................................................
....................................................................................... Post Code: ...........................................................................
Tel No: .................................................................... Email: .......................................................................................
Engineers Company: ..........................................................................................................................................
Tel No: ...................................................................... Email: ....................................................................................
Instalation Date: ....................................................................................................................................................
Engineers Name: ...................................................................................................................................................
Engineers Signature: ...........................................................................................................................................
6. Protection Function
7. Control Patterns
5. Thermostat Functions
NSB (Night SetBack) Function
NSB Mode depends on the NSB wired connection.
0V = NSB OFF
230V= NSB ON
The NSB signal is activated every 1 second. When the signal is received the
setpoint temperature will be set at ±2°C or ±4°C.
Heating and Cooling Selection
The Heating/Cooling function is determined by the CO terminal connection.
CO 0V = Heat mode
CO 230V= Cool mode
Cooling Blocked function
Cooling Enabled:
Set the jumper on ON . The thermostat will run in normal cooling mode.
That means that it will open/close the actuators when necessary. The LED will be
BLUE when the cooling function is running.
Cooling Disabled:
Set the jumper on OFF . The actuator will be closed and the LED will
be off.
Heat cut o at high/low temperature:
When room temperature is over 36°C or under 4°C, all heating/cooling outputs
will be turned off.
Short cycle protection:
When Cooling Mode is enabled the minimum interval between Relay ON/OFF
is 3 minutes.
Valve Protection:
Set the jumper on ‘ON’ to disable the function or on ‘OFF’ to enable it. Turn on the
valve for 5 minutes every week to prevent any damage to the valve.
Sensor Malfunction:
If the temperature sensor or temperature sensor compensation is open the LED
will flash BLUE/RED alternatively.
If CO terminal is connected and the Heating Mode is ON, the PWM function
will be activated.
If CO terminal is disconnected and the Cooling Mode is ON the ON/OFF control
output will be activated.
1

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Salus HTR230 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Salus HTR230 in de taal/talen: Engels als bijlage per email.

De handleiding is 2,17 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van Salus HTR230

Salus HTR230 Gebruiksaanwijzing - Nederlands - 2 pagina's

Salus HTR230 Gebruiksaanwijzing - Deutsch - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info