BA FU40knx Anwendungsprogramm HM; DE,GB - 23005 - ED – V09
* Functions available in ETS application program FU 40.00 knx Version 4.0, only in combination with hardware manufactured in CW16/2017 or later.
INSTRUCTION MANUAL ENGLISH PAGE 3 / 3
Parameters
Parameter light control
You have the possibility to send the lux value to the bus and/or to activate a light
control: lux switching (functionality like a twilight switch). Depending on your
parameter settings (Lux threshold / -hysteresis / -delay) the light control works
like a twilight switch and sends a switching bit or a scene to the bus when
reaching the lux thresholds. Additionally you have the option to activate an Extra
time switch. With this function you can program further switching times (OFF /
ON) with an adjustable duration (e.g. for energy saving solutions).
LUX LOGIC:
LUX THRESHOLD: Set the thresholds for the lux switching (ON / OFF).
FURTHER LUX THRESHOLD: You can set a further lux threshold.
LUX DELAY ON or OFF: It is possible to set a delay to avoid undesirable
switching due to disturbing light sources, e.g., car lights.
LUX HYSTERESIS: It is possible to set a hysteresis to avoid undesirable
switching due to disadvantageous positioning of the sensor, e.g., close to a
yard light.
Adjustments / Description
Values
Send measurement value
never, on query, on query and automatic/cyclic, on query
and change, on query and change and automatic/cyclic
Cycle interval for measurement value
every 30 seconds, every minute, every hour, every 6
hours, every 12 hours, at 00:00 am, at 00:02 am
Send upon x[%] change of measured value
1 50
Lux switching
Inactive/active
Light control depending on internal measurement or external bus value
Measurement value (intern), Bus (extern)**
Lux logic
ON at darkness / OFF at brightness,
OFF at darkness / ON at brightness
Threshold 2
Inactive/active
Extra time switch
Inactive/active
Settings for threshold 1 / treshold 2:
Threshold in [lux]
1 220.000 Lux
Hysteresis in [%]
0 50
Delay darkness in [s]
0 3600
Delay brightness in [s]
0 3600
Switching bit or scene
Switching bit, scene
Scene number for switching on
1 64
Scene number for switching off
1 64
* Enable blocking object
No/Yes
* Behaviour of blocking object
Block on 1 / Block on 0
* Condition after reset
Released / Blocked
* Behaviour when released
No action / Send current value
* Behaviour when blocked
No action / Send telegram
* Telegram when blocked
0/1 or scene number 1-64
Switch OFF
Inactive/active
Switch off from [hour], [minute]
00:00 23:59
Switch off to [hour], [minute]
00:00 23:59
Switch ON
Inactive/active
Switch on from [hour], [minute]
00:00 23:59
Switch on to [hour], [minute]
00:00 23:59
Parameters
Parameter temperature control
You have the possibility to send the temperature values to the bus and/or to
activate a temperature control (by activating the temperature threshold).
Depending on your parameter settings (Temperature setpoint + Delay
temperature setpoint + Temperature hysteresis) the temperature control sends a
switching bit or a scene to the bus when reaching the temperature thresholds.
TEMPERATUR LOGIC:
Adjustments / Description
Values
Send measurement value
never, on query, on query and automatic/cyclic, on query
and change, on query and change and automatic/cyclic
Cycle interval for measurement value
every 30 seconds, every minute, every hour, every 6
hours, every 12 hours, at 00:00 am, at 00:02 am
Send upon x*[0.C] change of measured value
1 255
Temperature threshold
Inactive/active
Temperature control depending on internal measurement or external bus
value
Measurement value (internal), Bus (external)**
Temperature setpoint in [0.1°C]
-500…+1000
Temperature hysteresis in [0.1°C]
1 600
Delay temperature setpoint in [s]
0 3600
Temperature logic
T > setpoint (cooling), T < setpoint (heating)
Switching bit or scene
Switching bit, scene
Scene number for switching on
1 64
Scene number for switching off
1 64
* Enable blocking object
No/Yes
* Behaviour of blocking object
Block on 1 / Block on 0
* Condition after reset
Released / Blocked
* Behaviour when released
No action / Send current value
* Behaviour when blocked
No action / Send telegram
* Telegram when blocked
0/1 or scene number 1-64
* Functions available in ETS application program FU 40.00 knx Version 4.0, only in combination with hardware manufactured in CW16/2017 or later.
** Definition „Receiver (internal) / Measurement value (internal)“: If „Receiver (internal)“ or „Measurement value (internal)“ is selected
the measurements provided by the FU40.00knx will be used and will also be send to the bus!
Definition „Bus (external)“: If „Bus (external)“ is selected the values provided from the bus will be used but still the measured
values of the FU40.00knx will be send to the bus!
6

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Muller FU 40.00 knx bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Muller FU 40.00 knx in de taal/talen: Duits, Engels als bijlage per email.

De handleiding is 0,3 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van Muller FU 40.00 knx

Muller FU 40.00 knx Gebruiksaanwijzing - Deutsch, English - 2 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info