INSTRUCTIONS INSTALLATION
ATTENTION
Installation of the gas fireplace heater, may only be carried out by a qualified person with the appropriate
authorization. The connection to the gas system, the connection of the flue pipe, wall and roof penetrations,
and all kinds of elements used for the installation of the fireplace should be made in accordance with the
standards of the construction law in force in the country and region where the heater is installed.
LOCATION OF DEVICE
Gas heaters of the CALMApowers series should be installed on a stable, non-combustible surface that has the required no-
tability. The device should be placed a minimum of 1.2 meters from combustible materials. The location of the heater should provide the
least number of bends of the coaxial system that works with it, and ensure the easiest possible routing of the gas supply line.
The fireplace should be located a minimum of 30 mm from noncombustible walls. The increase in the temperature of the walls
exposed directly to the fireplace should not exceed the ambient temperature by more than 80
°C. The heater is equipped with feet with infinitely adjustable height in the range of 0-25 mm. The use of feet allows you to level the
cartridge without problems.
CALMAmog heaters can be delivered to the customer complete with a dedicated housing, providing simple installation and the
required expansion joints necessary for proper operation of the fireplace. The enclosure, together with the appliance, should
be installed on a non-combustible surface. The appliance, including the enclosure, should be placed a minimum of 1.2 meters
from combustible materials. Between the rear wall of the enclosure and the noncombustible wall on which the set is installed,
a gap of at least 20 mm should be maintained.
ATTENTION
Gas heaters that work with heavier-than-air gases may not be installed in rooms below ground level, as well
as in rooms with ventilation ducts, the termination of which is located in a place where gas can
accumulate without the possibility of drainage.
INSTALLATION CHIMNEY
CALMA series gas heaters have been adapted for cooperation with concentric air and flue gas systems from POUJOULAT,
model BI-GAS and DUO-GAS in sizes 150/100. These systems work in negative pressure, which eliminates the need to stand
additional seals. The individual elements are connected to each other using a dedicated clamp. The system is made of acid-
resistant steel and can be used in solutions where the temperature of flue gases in the heater does not exceed 600 °C. The
systems can be purchased directly from the appliance manufacturer, from online stores or from local stores
listed at
www.poujoulat.pl. The chimney systems used for Hitze gas appliances can be routed
out through the side wall of the building (type
C11 system), through the roof (type C31 system), or use an existing co- min (type C91). Connection under the chimney system,
system routing, distances from combustible materials, roof and wall penetrations, sealing and insulation should be made in
accordance with the relevant regulations of the country or region where the appliance is installed. When designing the chimney
system, all impediments related to wind pressure on the terminal should be taken into account.