9 Bijlage 9.4 EDE-bestand voor praktijkvoorbeeld 1
9.4 EDE-bestand voor praktijkvoorbeeld 1
PROJECT_NAME: Sample EDE file for reference installaon.
VERSION_OF_REFERENCEFILE:
27
TIMESTAMP_OF_LAST_CHANGE:
AUTHOR_OF_LAST_CHANGE:
John Smith
VERSION_OF_LAYOUT:
2.3
#mandatory
mandator mandatory mandatory mandatory oponal
# keyname
device obj.-
instance
object-name object-type object-instance descripon
Device:1601395
1234 WC Vorraum Herren 8 1234 BACnet Interface of Geberit products to be connected to a Building Management System
StructuredView:0
1234 Gateway 29 0 Gateway
CharStringValue:1
1234 Gateway.DeviceSerial 40 1 Serial number of the gateway
NetworkPort:1
1234 BACstac-NPO-1 56 1
CharStringValue:2
1234 Gateway.ZoneName 40 2 Name of the zone/room the gateway is assigned to
BinaryValue:102
1234 Gateway.GenericInfo 5 102 The gateway has an info
BinaryValue:103
1234 Gateway.GenericWarning 5 103 The gateway has a warning
BinaryValue:104
1234 Gateway.GenericError 5 104 The gateway has an error
BinaryValue:107
1234 Gateway.UsageAcve 5 107 Pairing bu!on on gateway is currently pressed
MulStateValue:201
1234 Gateway.Locate 19 201 Used to locate the gateway (writable)
MulStateValue:202
1234 Gateway.DisableRadio 19 202 Used to switch on and off the radio interfaces in gateway (writable)
StructuredView:186000
1234 Zone.1.AllDevices 29 186000 Collecon group for all devices
CharStringValue:186002
1234 Zone.1.AllDevices.ZoneName 40 186002 Name of the zone/room the device is assigned to
MulStateValue:186101
1234 Zone.1.AllDevices.ConneconStatus 19 186101 State of the connecon between gateway and device (Collecon group)
BinaryValue:186103
1234 Zone.1.AllDevices.GenericWarning 5 186103 The device has a warning (Collecon group)
BinaryValue:186104
1234 Zone.1.AllDevices.GenericError 5 186104 The device has an error (Collecon group)
BinaryValue:186106
1234 Zone.1.AllDevices.LowBa!ery 5 186106 Ba!ery in the device is low (Collecon group)
BinaryValue:186107
1234 Zone.1.AllDevices.UsageAcve 5 186107 Device is currently in use (Collecon group)
BinaryValue:186108
1234 Zone.1.AllDevices.ValveOpen 5 186108 Valve in the device is currently opened (Collecon group)
PosiveIntegerValue:186140
1234 Zone.1.AllDevices.UsageCount 48 186140 Counts the usages of the device (Collecon group)
PosiveIntegerValue:186141
1234 Zone.1.AllDevices.FlushCount 48 186141 Counts the flushes of the device (Collecon group)
PosiveIntegerValue:186147
1234 Zone.1.AllDevices.HygieneFlushCount 48 186147 Counts the flushes based on local hygiene programs of the device (Collecon group)
PosiveIntegerValue:186170
1234 Zone.1.AllDevices.WaterUsage 48 186170 Indicates the water usage of the device (Collecon group)
MulStateValue:186207
1234 Zone.1.AllDevices.Cleaning 19 186207 Used to switch on and off the cleaning mode of the device (writable) (Collecon group)
StructuredView:223200
1234 Zone.1.AllWashbasins 29 223200 Collecon group for all washbasins
CharStringValue:223202
1234 Zone.1.AllWashbasins.ZoneName 40 223202 Name of the zone/room the device is assigned to
MulStateValue:223301
1234 Zone.1.AllWashbasins.ConneconStatus 19 223301 State of the connecon between gateway and device (Collecon group)
BinaryValue:223303
1234 Zone.1.AllWashbasins.GenericWarning 5 223303 The device has a warning (Collecon group)
BinaryValue:223304
1234 Zone.1.AllWashbasins.GenericError 5 223304 The device has an error (Collecon group)
BinaryValue:223306
1234 Zone.1.AllWashbasins.LowBa!ery 5 223306 Ba!ery in the device is low (Collecon group)
BinaryValue:223307
1234 Zone.1.AllWashbasins.UsageAcve 5 223307 Device is currently in use (Collecon group)
BinaryValue:223308
1234 Zone.1.AllWashbasins.ValveOpen 5 223308 Valve in the device is currently opened (Collecon group)
PosiveIntegerValue:223340
1234 Zone.1.AllWashbasins.UsageCount 48 223340 Counts the usages of the device (Collecon group)
PosiveIntegerValue:223341
1234 Zone.1.AllWashbasins.FlushCount 48 223341 Counts the flushes of the device (Collecon group)
PosiveIntegerValue:223347
1234 Zone.1.AllWashbasins.HygieneFlushCount 48 223347 Counts the flushes based on local hygiene programs of the device (Collecon group)
PosiveIntegerValue:223370
1234 Zone.1.AllWashbasins.WaterUsage 48 223370 Indicates the water usage of the device (Collecon group)
MulStateValue:223407
1234 Zone.1.AllWashbasins.Cleaning 19 223407 Used to switch on and off the cleaning mode of the device (writable) (Collecon group)
StructuredView:223600
1234 Zone.1.Washbasin.1 29 223600 Lavatory Tap IFP
CharStringValue:223601
1234 Zone.1.Washbasin.1.DeviceSerial 40 223601 Serial number of the device
CharStringValue:223602
1234 Zone.1.Washbasin.1.ZoneName 40 223602 Name of the zone/room the device is assigned to
MulStateValue:223701
1234 Zone.1.Washbasin.1.ConneconStatus 19 223701 State of the connecon between gateway and device
BinaryValue:223703
1234 Zone.1.Washbasin.1.GenericWarning 5 223703 The device has a warning
BinaryValue:223704
1234 Zone.1.Washbasin.1.GenericError 5 223704 The device has an error
BinaryValue:223706
1234 Zone.1.Washbasin.1.LowBa!ery 5 223706 Ba!ery in the device is low
BinaryValue:223707
1234 Zone.1.Washbasin.1.UsageAcve 5 223707 Device is currently in use
BinaryValue:223708
1234 Zone.1.Washbasin.1.ValveOpen 5 223708 Valve in the device is currently opened
PosiveIntegerValue:223740
1234 Zone.1.Washbasin.1.UsageCount 48 223740 Counts the usages of the device
PosiveIntegerValue:223741
1234 Zone.1.Washbasin.1.FlushCount 48 223741 Counts the flushes of the device
PosiveIntegerValue:223747
1234 Zone.1.Washbasin.1.HygieneFlushCount 48 223747 Counts the flushes based on local hygiene programs of the device
PosiveIntegerValue:223770
1234 Zone.1.Washbasin.1.WaterUsage 48 223770 Indicates the water usage of the device
MulStateValue:223801
1234 Zone.1.Washbasin.1.Locate 19 223801 Used to locate the device (writable)
PosiveIntegerValue:223803
1234 Zone.1.Washbasin.1.DrainVolume 48 223803 Used to open the valve of the device for a requested amount of water (writable)
MulStateValue:223807
1234 Zone.1.Washbasin.1.Cleaning 19 223807 Used to switch on and off the cleaning mode of the device (writable)
StructuredView:224000
1234 Zone.1.Washbasin.2 29 224000 Lavatory Tap IFP
CharStringValue:224001
1234 Zone.1.Washbasin.2.DeviceSerial 40 224001 Serial number of the device
CharStringValue:224002
1234 Zone.1.Washbasin.2.ZoneName 40 224002 Name of the zone/room the device is assigned to
MulStateValue:224101
1234 Zone.1.Washbasin.2.ConneconStatus 19 224101 State of the connecon between gateway and device
BinaryValue:224103
1234 Zone.1.Washbasin.2.GenericWarning 5 224103 The device has a warning
BinaryValue:224104
1234 Zone.1.Washbasin.2.GenericError 5 224104 The device has an error
BinaryValue:224106
1234 Zone.1.Washbasin.2.LowBa!ery 5 224106 Ba!ery in the device is low
BinaryValue:224107
1234 Zone.1.Washbasin.2.UsageAcve 5 224107 Device is currently in use
BinaryValue:224108
1234 Zone.1.Washbasin.2.ValveOpen 5 224108 Valve in the device is currently opened
PosiveIntegerValue:224140
1234 Zone.1.Washbasin.2.UsageCount 48 224140 Counts the usages of the device
PosiveIntegerValue:224141
1234 Zone.1.Washbasin.2.FlushCount 48 224141 Counts the flushes of the device
PosiveIntegerValue:224147
1234 Zone.1.Washbasin.2.HygieneFlushCount 48 224147 Counts the flushes based on local hygiene programs of the device
PosiveIntegerValue:224170
1234 Zone.1.Washbasin.2.WaterUsage 48 224170 Indicates the water usage of the device
MulStateValue:224201
1234 Zone.1.Washbasin.2.Locate 19 224201 Used to locate the device (writable)
PosiveIntegerValue:224203
1234 Zone.1.Washbasin.2.DrainVolume 48 224203 Used to open the valve of the device for a requested amount of water (writable)
MulStateValue:224207
1234 Zone.1.Washbasin.2.Cleaning 19 224207 Used to switch on and off the cleaning mode of the device (writable)
StructuredView:224400
1234 Zone.1.Washbasin.3 29 224400 Lavatory Tap IFP
CharStringValue:224401
1234 Zone.1.Washbasin.3.DeviceSerial 40 224401 Serial number of the device
CharStringValue:224402
1234 Zone.1.Washbasin.3.ZoneName 40 224402 Name of the zone/room the device is assigned to
MulStateValue:224501
1234 Zone.1.Washbasin.3.ConneconStatus 19 224501 State of the connecon between gateway and device
BinaryValue:224503
1234 Zone.1.Washbasin.3.GenericWarning 5 224503 The device has a warning
BinaryValue:224504
1234 Zone.1.Washbasin.3.GenericError 5 224504 The device has an error
BinaryValue:224506
1234 Zone.1.Washbasin.3.LowBa!ery 5 224506 Ba!ery in the device is low
BinaryValue:224507
1234 Zone.1.Washbasin.3.UsageAcve 5 224507 Device is currently in use
BinaryValue:224508
1234 Zone.1.Washbasin.3.ValveOpen 5 224508 Valve in the device is currently opened
PosiveIntegerValue:224540
1234 Zone.1.Washbasin.3.UsageCount 48 224540 Counts the usages of the device
PosiveIntegerValue:224541
1234 Zone.1.Washbasin.3.FlushCount 48 224541 Counts the flushes of the device
PosiveIntegerValue:224547
1234 Zone.1.Washbasin.3.HygieneFlushCount 48 224547 Counts the flushes based on local hygiene programs of the device
PosiveIntegerValue:224570
1234 Zone.1.Washbasin.3.WaterUsage 48 224570 Indicates the water usage of the device
MulStateValue:224601
1234 Zone.1.Washbasin.3.Locate 19 224601 Used to locate the device (writable)
PosiveIntegerValue:224603
1234 Zone.1.Washbasin.3.DrainVolume 48 224603 Used to open the valve of the device for a requested amount of water (writable)
MulStateValue:224607
1234 Zone.1.Washbasin.3.Cleaning 19 224607 Used to switch on and off the cleaning mode of the device (writable)
StructuredView:224800
1234 Zone.1.Washbasin.4 29 224800 Lavatory Tap IFP
CharStringValue:224801
1234 Zone.1.Washbasin.4.DeviceSerial 40 224801 Serial number of the device
CharStringValue:224802
1234 Zone.1.Washbasin.4.ZoneName 40 224802 Name of the zone/room the device is assigned to
MulStateValue:224901
1234 Zone.1.Washbasin.4.ConneconStatus 19 224901 State of the connecon between gateway and device
BinaryValue:224903
1234 Zone.1.Washbasin.4.GenericWarning 5 224903 The device has a warning
BinaryValue:224904
1234 Zone.1.Washbasin.4.GenericError 5 224904 The device has an error
BinaryValue:224906
1234 Zone.1.Washbasin.4.LowBa!ery 5 224906 Ba!ery in the device is low
BinaryValue:224907
1234 Zone.1.Washbasin.4.UsageAcve 5 224907 Device is currently in use
BinaryValue:224908
1234 Zone.1.Washbasin.4.ValveOpen 5 224908 Valve in the device is currently opened
PosiveIntegerValue:224940 1234 Zone.1.Washbasin.4.UsageCount 48 224940 Counts the usages of the device
30.03.2023 12:47
108 27021606314557707 © 11-2023
972.115.00.0(01)
108

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Geberit Connect bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Geberit Connect in de taal/talen: Nederlands als bijlage per email.

De handleiding is 5,28 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info