C.s.lo.= Control set point lower limit.(for
selected output)
Adjustable between 0 and C.s.Hi.
C.s.Hi.= Control setpoint upper limit.(for
selected output)
Adjustable between C.s.Lo. and Upper scale
value.
a2.s.l= Alarm2 set value lower limit.
Adjustable between 0 and A2.S.H
parameter value.
a2.s.H= Alarm2 set value upper limit.
Adjustable between A2.S.L
parameter value and upper scale
value.
a2.Hy = Hysteresis of the Alarm2
output.
Adjustable between 1 and 50 °C.
A2.st. = The state of Alarm2 output.
Hi = If A2 output is above the set
value. (on)
lo = If A2 output is above the set
value (off).
A2.Er. = State of Alarm2 output in the
case of sensor failure.
on = A2 output is probe failure (on).
off= A2 output is probe failure (off).
A2.tp = Function of Alarm2 type.
Four kinds of functions can be
selected.
indE. = Independdnt alarm
(Independent)
dE. = Deviation
bAnd = Band alarm (Band)
bAn.i = Band with inhibition
inp.t. = Input type selection.
Pt.0 = PT100 Decimal,
Pt = PT100,
FE.cn.= J type,
nc.nA.= K type,
c.cn. = T type,
p10.r.= S type,
P13.r.= R type thermocouple selection.
This parameter varies when changing
some parameters.
Unit = The temperature unit.
°C = °C, °F= °F
(This parameter varies when
changing some parameters.)
C.o.sE = Control output selection
C-A2 = C/A2 (Relay) output selection
SSR = SSR output selection
F.kE.C. = Function key setting parameter
nonE = Function key is off.
C2.S.A. = The function key with 2.set value is used.
manu. = Manual mode can be achieved with the function key.
dSP.o. = Only the temperature display mode is entered with
function key.
C. Pb = Proportional band.(for selected
output)
Adjustable between %0.0 and %100.0.
C. Pb = %0.0,On-Off control is selected.
C. ti = Integral time.(for selected output)
Adjustable between 0 and 100.0 minutes.
C. ti = 0.0,integral impact is disable.
parameter is different from “0”,this
parameter appears.
C. Pb
C.Hys = Hysteresis of the output.(for
selected output)
Adjustable between 1 and 50 °C.
= 0,this parameter is active.C. Pb
C. td = Derivative time.(for selected output)
Asjustable between 0.00 and 25.00 minutes.
C. td = 0.0, derivative time is disabled.
parameter is different from”0”,this
parameter appears.
C. Pb
C. Ct. = Period time.(for selected output)
Adjustable between 1 and 250 second.
parameter is different is different
from“0”,this parameter appears.
C. Pb
C.p.st = The ratio of output power at the
setpoint.Adjustable between %0 and %100.
C.E.P.s. = The percentage of faulty sensor
selected output power.
Adjustable between %0 and %100.
C.typ. = Control output type
C.typ. = HEAt means heating control.
C.typ. = CooL means cooling control.
While the parameter names appear, if and
keys are pressed together, returns to the program mode.
S.Cod = Security menu access
code.
It should be 2011.
Cosc. = Parameters of CoN.o.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
P. no = Only visible.
m.SEt. = The percentage of manual output parameter.
Adjustable between %0 and %100.
This parameter allows manual adjustment of the output
power when the manual output selection.
C. Pb.= 0, this parameter is not seen.
If co.SE parameter is different
from C-A2, this parameter is seen.
a.2.sc. = Parameters of al2.o.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
P. no = Only visible.
Co.sc. = Parameters of Conf.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
P. no = Only visible.
S.t.Sc. = Parameters of S.tun.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
Co.sc. = Parameters of Conf.
menu security access level code.
no = Parameter settings are not
change.
yEs = Parameter setting will be
restored.
2/4
C.s.Lo.
C.s.Hi.
C. pb
C. ti
C. td
C.p.st
C.Hys
C. Ct.
C.typ
s.s.t.s.
C.E.p.s.
Con.o.
AL2.o.
ConF.
S.tun.
SEcu.
S.Cod.
Co.sc.
m.SEt.
a.2.sc.
Cn.sc.
S.t.sc.
dEF.P.
inp.t.
Unit
fltr.
C.o.sE
offs.
s.t.Co.
F.k.E.C.
A2.S.L
A2.S.H
A2.HY
A2.tP
A2.St.
A2.Er.
SET
SET
SET
SET
SET
F
Programming mode
This parameter indicates the time to reach set point
value when the device is first energised.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable and the
device reaches set point value quickly.
Setting Pb = 0, soft start feature will be disabled.
Sst.S =Sofy starter timer set value
fLtr. = Coefficient of digital filter.
Filter for display value.
Adjustable between 1 and 200. If this parameter is 1,
digital filter runs most quick. If the parameter is 200,
the filter run most slow. The value of parameter should
be increased in interference.
oFfS. =
Offset value is added to the measurement value.
Adjusted between -100 and +100°C.The normal value is 0.
Offset value.
St.Cu = Self tune control parameter.
If both keys are pressed ,yEs
message is displayed on the screen
and selftune process is started
automatically.
If both keys are pressed, no
message is displayed on the screen
and selftune process is stopped.
SET
If key is pressed while holding key, the programming mode is enabled.
SET
F
Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
Alternatively, the same function occurs first pressing key and key is pressing programming mode is entered.Then and keys are pressing
together, data is recorded and running mode is entered.
Modification Of Parameter Diagram
When holding key, the value of parameter flashes and using
keys the requested value can be adjusted.
If key is pressed and held 0.6 seconds, the value of the selected
parameter changes rapidly. If waited enough,the value increases 100 at each
step. After 1 second following the release of the key, initial condition is
returned.The same procedure is valid for the decrement key.
Chys
6
5
6
SET
SET SET
SET
C.s.lO.
inp.t.
A2.s.l
Co.sc.
C1.sE.
C.s.Hi.
Unit
A2.s.H
A2.Sc.
C2.SE.
C. PB
Fltr.
A2Hy.
Cn.Sc.
A2.SE.
C.HyS
C.o.SE.
A2.tp
S.t.Sc.
C. ti
offs.
a2.st.
dEf.P.
C. td
f.k.E.C.
a2.Er.
a2.Er.
C. Ct.
m.sEt.
C.P.St.
C.EP.S.
S.s.t.S.
C.typ.
TC input
TC input
TC input
TC input
TC input
PT100 input
PT100 input
PT100 input
PT100 input
PT100 input
0
FE.cn.
0
0
25
2
2
C-A2
indE
P.yEs
P.yEs
400
P.yEs
400
P.yEs
500
4.0
0
Hi
no
1.00
nonE
on
no
20
50
0
0
0
HEat
-200
Pt.
-200
600
°C
600
DEFAULT PARAMETERS
Set parameters
Control output
parameters
Alarm2 output
parameters
Configuration
parameters
Self tune
parameters
Security
parameters
SET
SET
ET2011-E-06-201408
When the self tune begins,
PIdt. message
and measurement value are shown
alternately.
After the completion of the self tune process,
st.Co. parameter is automatically changed to
no and the device returns to working mode.
If the measured temperature is higher than
90% of the set value at the beginning of the
self tune process, then tE.Hi. message is
shown alternately and the measured
temperature is waited to go below %60 of
the set value. After that, self tune operation
is started automatically.
If it is intended to abort the self tune
process, St.Co. parameter is changed to
no and key is pressed.
2

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Enda ET2011 PID bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Enda ET2011 PID in de taal/talen: Engels als bijlage per email.

De handleiding is 0,31 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Andere handleiding(en) van Enda ET2011 PID

Enda ET2011 PID Gebruiksaanwijzing - Deutsch - 4 pagina's


Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info