PIPE FITTINGS
All pipe ttings are made via 22mm compression
ttings directly to the unit. The ttings are threaded
3/4”BSP male parallel, should threaded pipe
connections be required.
COLD FEED
A 22mm cold water supply is recommended, however,
if a 15mm (1/2”) supply exists, which provides sufcient
ow, this may be used (although more ow noise
may be experienced).
A stopcock or servicing valve should be incorporated
into the cold water supply to enable the cylinder and
its associated controls to be isolated and serviced.
COLD WATER COMBINATION VALVE ASSEMBLY
The 2-piece cold water combination valve assembly
(see Fig. 2) can be located anywhere on the cold
water mains supply prior to the expansion vessel
(see Fig. 6 Page 10) but the two pieces do not have
to be installed together.
The pressure reducing valve incorporates the
pressure reducer and strainer and the expansion valve
incorporates the expansion and check valves. Ensure
that the valves are installed in the correct order
and orientation. No other valves should be placed
between the expansion valve and the cylinder. A
connection can be made between the expansion and
pressure reducing valves to provide a balanced cold
water connection. The expansion valve connection
must not be used for any other purpose.
DRAIN TAP
A suitable draining tap should be installed in the cold
water supply to the cylinder between the expansion
valve (see Fig. 6 Page 10) and the heater at as low a
level as possible. It is recommended that the outlet
point of the drain pipework be at least 1 metre below
the level of the heater (this can be achieved by
attaching a hose to the drain tap outlet spigot).
EXPANSION VESSEL
The expansion vessel accommodates expansion
that results from heating the water inside the unit.
The expansion vessel is pre-charged at 0.35MPa
(3.5 bar). The expansion vessel must be connected
between the expansion valve and the cylinder (see
Fig. 6 Page 10). The location of the expansion
vessel should allow access to recharge the pressure
as and when necessary, this can be done using
a normal car foot pump. It is recommended that
the expansion vessel is adequately supported. An
expansion vessel wall mounting bracket is supplied
for this purpose and should be tted.
SECONDARY CIRCULATION
If secondary circulation is required it is recommended
that it be connected to the cylinder as shown (see
Fig. 3 page 5) via a swept tee joint into the cold
feed to the unit. A swept tee joint is available as an
accessory (order code no. 5133565).
The secondary return pipe should be in 15mm pipe
and incorporate a check valve to prevent backow.
A suitable WRAS approved bronze circulation
pump will be required. On large systems, due to
the increase in system water content, it may be
necessary to t an additional expansion vessel to the
secondary circuit. This should be done if the capacity
of the secondary circuit exceeds 10 litres.
Pipe capacity (copper):
15mm O.D. = 0.13 l/m (10 litres = 77m)
22mm O.D. = 0.38 l/m (10 litres = 26m)
28mm O.D. = 0.55 l/m (10 litres = 18m)
NOTE: Secondary circulation is NOT recommended for
direct electric units.
OUTLET
The hot water outlet is a 22mm compression tting
located at the top of the cylinder. Hot water distribution
pipework should be 22mm pipe with short runs of
15mm pipe to terminal ttings such as sinks and
basins. Pipe sizes may vary due to system design.
INSTALLATION GENERAL
Fig. 2: Cold water combination valve assembly
Fig. 3: Secondary circulation connection
5

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Elson Zircon bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Elson Zircon in de taal/talen: Engels als bijlage per email.

De handleiding is 2,28 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info