577306
2
Verklein
Vergroot
Pagina terug
1/20
Pagina verder
PROFIPOL
®
Benning Elektrotechnik & Elektronik GmbH & Co. KG
Münsterstraße 135 - 137 • D - 46397 Bocholt
Phone: +49 (0) 2871 - 93 - 0 • Fax: +49 (0) 2871 - 93 - 429
www.benning.de • E-Mail: duspol@benning.de
T.-Nr. 755737.12 / 03.2013
D
Bedienungsanleitung
Operating manual
F
Mode d‘emploi
E
Manuel de instrucciones
Инструкция за експлоатация
Návod k použití zkoušečky
Brugsanvisning
Käyttöohje
Οδηγίες χρήσεως
H
Használati utasítás
I
Istruzioni per l’uso
Naudojimosi instrukcija
N
Bruksanvisning
Gebruiksaanwijzing
Instrukcja obsługi
Instrucţiuni de utilizare
Инструкция по эксплуатации
индикатора напряжения
S
Bruksanvisning
Kullanma Talimati
Priručnik za upotrebu
Operating manual
PROFIPOL
®
Before using the voltage tester PROFIPOL
®
:
Please read the operating manual carefully and
always observe the safety instructions!
List of contents:
1. Safety instructions
2. Functional description of the voltage tester
3. Functional test of the voltage tester
4. How to test AC voltages
5. How to test DC voltages
5.1 How to test the polarity at DC voltage
6. Technical data
7. General maintenance
8. Environmental notice
1. Safety instructions:
- Hold the voltage tester only by the insulated han-
dles and
and do not touch the contact elec-
trodes (probe tips) !
- Immediately before use: Check the voltage tester
for correct operation! (see chapter 3). The voltage
tester must not be used if one or several display
functions fail or if the voltage tester is not ready to
operate (DIN EN 61243-3:2011)!
- The voltage tester must be used only within the
nominal voltage range of 6 V up to 400 V!
- The voltage tester must be used only in electric
circuits of overvoltage category CAT III with max.
300 V for phase-to-earth measurements.
- The voltage tester complies with protection class
IP 65 and therefore can also be used under wet
conditions.
- For testing, firmly grasp the voltage tester by the
handles and .
- The voltage tester is designed for being used by
qualified electricians and under safe working con-
ditions.
- The LED step indicator is intended for indicating
the voltage range. It is not intended for measuring
purposes.
- Typical values of noise voltages are not displayed,
they are suppressed.
- Never connect the voltage tester to voltage for
longer than 30 seconds (maximum permissible
operating time = 30 s)!
- The voltage tester only operates correctly
within the temperature range of - 15 °C up to
+ 55 °C at relative air humidity of 20 % up to
96 %.
- Do not dismantle the voltage tester!
- Please protect the housing of the voltage tester
against contamination and damages.
- Please store the voltage tester under dry conditions.
Attention:
After maximum load (i.e. after a measurement of 30
seconds at 400 V), the voltage tester must not be used
for a duration of 300 seconds!
Electrical symbols on the device:
Symbol Meaning
Important documentation!
The symbol indicates that the guide
described in the manual, to avoid any
risks
Device or equipment for working under
voltage
Direct and alternating voltage (DC/AC)
Earth (voltage to ground)
2. Functional description
The PROFIPOL
®
is a two-pole voltage tester accord-
ing to DIN EN 61243-3:2011 with visual display
and without own power supply. The voltage tester is
designed for DC and AC voltage tests within the volt-
age range of 6 V up to 400 V. It can be used to per-
form polarity tests in DC.
The voltage tester consists of the test probes L1
and L2 and a connecting cable 6. The test probe
L1 is equipped with a display .
Display field
The display system consists of high-contrast light-
emitting diodes (LED) 3 indicating voltages in steps
of 6 V to 400 V. The indicated voltages are nominal
voltages. With DC voltage, the LEDs also indicate the
polarity (see chapter 5).
3. Functional check
- The voltage tester must be used only within the
nominal voltage range of 6 V up to 400 V!
- Never connect the voltage tester to voltage for
longer than 30 seconds (maximum permissible
operating time = 30 s)!
- Check the voltage tester for correct function
immediately before use!
- Test all functions by means of known voltage
sources.
For DC voltage tests use e.g. a car battery.
For AC voltage tests use e.g. a 230 V socket.
Do not use the voltage tester unless all functions are
operating correctly!
4. How to test AC voltages
- The voltage tester must be used only within the
nominal voltage range of 6 V up to 400 V!
- Never connect the voltage tester to voltage for
longer than 30 seconds (maximum permissible
operating time = 30 s)!
- Place the contact electrodes of the test probes
L1 and L2 against the relevant points of the
unit under test.
- For AC voltages from 6 V onwards the LEDs
“plus” and “minus” 4 and 5 light up. Further-
more, all LEDs light until the step value of the
applied voltage is reached.
5. How to test DC voltages
- The voltage tester must be used only within the
nominal voltage range of 6 V up to 400 V!
- Never connect the voltage tester to voltage for
longer than 30 seconds (maximum permissible
operating time = 30 s)!
- Place the contact electrodes of the test probes
L1 and L2 against the relevant points of the
unit under test.
- For AC voltages from 6 V onwards the LEDs
“plus” and “minus” 4 and 5 light up. Further-
more, all LEDs light until the step value of the
applied voltage is reached.
5.1 How to test the polarity at DC voltage
- The voltage tester must be used only within the
nominal voltage range of 6 V up to 400 V!
- Never connect the voltage tester to voltage for
longer than 30 seconds (maximum permissible
operating time = 30 s)!
- Place the contact electrodes of the test probes
L1 and L2 against the relevant points of the
unit under test.
- If LED 4 lights up, the “positive pole” of the unit
under test is at test probe .
- If LED 5 lights up, the “negative pole” of the unit
under test is at test probe .
6. Technical data
- Guideline for two-pole voltage testers: DIN EN
61243-3:2011
- Protection class: IP 65, IEC 60529 (DIN 40050)
IP 65 means: Protection against access to danger-
ous parts and protection against solid impurities,
dustproof, (6 - first index). Protected against water
jets, (0 - second index).
- Nominal voltage range: 6 V to 400 V
- Internal resistance, measuring circuit: 130 kΩ
- Current consumption:
max. I
n
3.1 mA
- Polarity indication: LED +; LED -
(indicating handle = positive polarity)
- Indicating steps LED: 6 V, 12 V, 50 V, 120 V, 230 V,
400 V
- max. indicating errors: U
n
± 15 %, ELV U
n
- 15 %
- Nominal frequency range f: 0 to 500 Hz
- max. permissible operating time:
ED = 30 s (max. 30 seconds), 300 s pause
- Weight: approx. 136 g
- Connecting cable length: approx. 830 mm
- Operating and storing temperature range: - 15 °C
up to + 55 °C (climate category N)
- Relative air humidity: 20 % up to 96 % (climate
category N)
7. General maintenance
Clean the exterior of the housing with a clean dry cloth
(exception: special cleansing cloths). Do not use sol-
vents and/ or abrasives to clean the voltage tester.
8. Environmental notice
At the end of the product’s useful life, please
dispose of it at appropriate collection points
provided in your country.
6
3
4
5
A
B
2

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Benning Profipol bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Benning Profipol in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Spaans, Pools, Turks, Deens, Zweeds, Noors, Fins als bijlage per email.

De handleiding is 2,25 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info