Data + power for all addressable detectors
The ATS1290 can support 16 detectors. For some modules, 2 inputs are
necessary, and therefore the expanded addressing mode could be
used to stay into the range of 32 addresses on the ATS1290.
Cable topology IADS – BUS (see fig )
A - DGP, B - control panel
In principle, the bus topology is free. Shown are several topologies (see
figure ):
1. Distributed (all IADS modules distributed across the line).
2. Star (all modules with own branches to a star point).
3. Lumped (all IADS modules at the end).
Recommended cable type
Use cables with as low resistance and capacitance as possible.
If a shielded cable is used for the IADS bus, this must not be connected
to either earth, PID- or PID+. If connected, it would result in additional
capacity and it will reduce the distance of the IADS bus.
The Table 1 below shows the maximum cable lengths in metres for
different cable types. The number of modules and module load are
taken into account. Check the module manuals for the "Unit Load". 1
Unit Load corresponds to 300 µA typical current.
The absolute minimum working voltage of the IADS DGP is
10.5 VDC with battery operation (measured on COMMS 12 VDC
power supply of the DGP).
Table 1. Maximum cable lengths (meters) with a minimum DGP voltage
of 10.5V
4 Wire IADS bus
External powered IADS modules
(4 wire IADS bus)
32 IADS modules:
AD011 (UL=1), AD111 (UL=2)
Cable type 2 x 0.5 mm 2 x 2 x 0.5 mm
# Wires 1 + 1 2 + 2
IADS bus 0.5 mm 1 mm
Distributed S 1 x 800 m 1 x 1600 m
Star T 16 x 200 m 16 x 400 m
U 1 x 80 m 1 x 880 m Lumped
V 16 x 40 m 16 x 40 m
2 Wire IADS bus
IADS modules powered out of the IADS bus
(2 wire IADS bus)
16 IADS modules:
EV435-AD (UL=8), EV435AM-AD (UL=16)
Cable type 2 x 0.5 mm 2 x 2 x 0.5 mm
# Wires 1 + 1 2 + 2
IADS bus 0.5 mm 1 mm
Distributed S 1 x 200 m 1 x 400 m
Star T 16 x 200 m 16 x 400 m
U 1 x 40 m 1 x 80 m Lumped
V 16 x 10 m 16 x 20 m
The distances S, T, U and V are referred to in Fig .
The power supply of conventional detectors is not taken into
account.
IADS module address setting and zone/output numbering
The address setting for the IADS module is directly linked to the zone
and output number the module will have in the control panel. IADS
module numbering starts from DIP switch setting 0.
Table 2. Address setting examples
1st DGP
address
Internal module
(e.g. EV435-AD) address
DIP switch setting on
internal module
17 0 00000000
18 1 10000000
19 2 01000000
4th DGP
address
Internal module
(e.g. EV435-AD) address
DIP switch setting on
internal module
65 0 00000000
66 1 10000000
67 2 01000000
15th DGP
address
Internal module
(e.g. EV435-AD) address
DIP switch setting on
internal module
241 0 00000000
242 1 10000000
243 2 01000000
Combine functionality to one output
For some applications, it is good practice to combine functionality to
one output to save outputs for other purposes. For example, enabling
and disabling walk test LEDs for the AD111.
Normally one output, of which can enable/disable the walk test LED, is
directly linked from the control panel to the IADS module. Each output
can control one walk test LED of one IADS module.
It is also possible to control all walk test LEDs of all AD111 by one
output. The only requirement is that the output needs to be within the
DGP range. Program the "ATS style output" for all relevant IADS
modules to one specific output. If more areas need to be controlled
separately, more outputs need to be reserved.
Learning IADS modules
IADS modules need to be recognised by the ATS1290 IADS DGP before
the device will be able to transfer status information or can be
configured by the IADS DGP.
To facilitate this, the ATS1290 IADS DGP has a jumper (JP2, fig , ).
Shorting this jumper with a screwdriver for a few seconds will start the
learn mode by which modules will become known. Any additional
settings regarding configuration of the module are available either by
jumper/DIP switch settings or via configuration menu, which is a part
of the ATS1290 menu. For more information on the available settings
of a module, see the manual of that module.
ATS1290 programming menu
The ATS1290 provides for additional settings available through the
onboard menu. To enter this menu:
Connect the ATS1290 to the ATS control panel.
In the ATS control panel Installation Programming menu:
o Activate polling to the ATS1290 (installer-menu 4).
o Enter installer-menu 28 – Remote Devices.
o Select 1-DGP.
o Select the ATS1290 DGP address.
You are now in the ATS1290 DGP menu.
Menu explanation
1. Status
Retrieve information regarding the status of the ATS1290.
Use the ENTER key to move through the different information screens.
1.1. Operational status
Indicates module status: DGP-Tamper, Module missing, multiple
modules, etc.
1.2. Device info
Shows in one line the number of modules known to the system, the
number of modules in alarm and the number of modules in tamper.
3
3

Hulp nodig? Stel uw vraag in het forum

Spelregels

Misbruik melden

Gebruikershandleiding.com neemt misbruik van zijn services uitermate serieus. U kunt hieronder aangeven waarom deze vraag ongepast is. Wij controleren de vraag en zonodig wordt deze verwijderd.

Product:

Bijvoorbeeld antisemitische inhoud, racistische inhoud, of materiaal dat gewelddadige fysieke handelingen tot gevolg kan hebben.

Bijvoorbeeld een creditcardnummer, een persoonlijk identificatienummer, of een geheim adres. E-mailadressen en volledige namen worden niet als privégegevens beschouwd.

Spelregels forum

Om tot zinvolle vragen te komen hanteren wij de volgende spelregels:

Belangrijk! Als er een antwoord wordt gegeven op uw vraag, dan is het voor de gever van het antwoord nuttig om te weten als u er wel (of niet) mee geholpen bent! Wij vragen u dus ook te reageren op een antwoord.

Belangrijk! Antwoorden worden ook per e-mail naar abonnees gestuurd. Laat uw emailadres achter op deze site, zodat u op de hoogte blijft. U krijgt dan ook andere vragen en antwoorden te zien.

Abonneren

Abonneer u voor het ontvangen van emails voor uw Aritech ATS1290 bij:


U ontvangt een email met instructies om u voor één of beide opties in te schrijven.


Ontvang uw handleiding per email

Vul uw emailadres in en ontvang de handleiding van Aritech ATS1290 in de taal/talen: Nederlands, Duits, Engels, Frans, Italiaans, Deens, Fins als bijlage per email.

De handleiding is 1,11 mb groot.

 

U ontvangt de handleiding per email binnen enkele minuten. Als u geen email heeft ontvangen, dan heeft u waarschijnlijk een verkeerd emailadres ingevuld of is uw mailbox te vol. Daarnaast kan het zijn dat uw internetprovider een maximum heeft aan de grootte per email. Omdat hier een handleiding wordt meegestuurd, kan het voorkomen dat de email groter is dan toegestaan bij uw provider.

Uw handleiding is per email verstuurd. Controleer uw email

Als u niet binnen een kwartier uw email met handleiding ontvangen heeft, kan het zijn dat u een verkeerd emailadres heeft ingevuld of dat uw emailprovider een maximum grootte per email heeft ingesteld die kleiner is dan de grootte van de handleiding.

Er is een email naar u verstuurd om uw inschrijving definitief te maken.

Controleer uw email en volg de aanwijzingen op om uw inschrijving definitief te maken

U heeft geen emailadres opgegeven

Als u de handleiding per email wilt ontvangen, vul dan een geldig emailadres in.

Uw vraag is op deze pagina toegevoegd

Wilt u een email ontvangen bij een antwoord en/of nieuwe vragen? Vul dan hier uw emailadres in.



Info